POPULACE

Generator Automatic Voltage Regulator Leroy Somer AVR R448

Model: R448

Compatible R448 generator AVR at factory wholesale price. 100% bench-tested, 13-month warranty, in stock. Request wiring diagram, datasheet & quote.

Warranty13 months
Place of OriginFujian, China
Brand NamePOPULACE
Model NumberR448
Overall Size215×150×65mm
Weight1.1kg
CertificationCE,ISO9001
Supply & Excitation SystemAREP auxiliary windings (X1, X2, Z1, Z2) or PMG system
Voltage Regulation< ±0.5% RMS steady-state accuracy
Excitation Current CapacityContinuous 10A, Forcing 10A for 10s (limit adjustable via P5: 4.5-10A)
Load Acceptance ModuleIntegrated LAM (~15% voltage drop relief), cut ST5 wire to suppress
Paralleling & Sensing0-110V/220V/380V sensing; C.T. ../1A droop input with P1 adjustment
Lead time2-3 days (in stock)

Applications

  • Standby and prime diesel generator sets fitted with Leroy Somer alternators in telecom, data-centre and hospital backup power
  • Commercial and industrial gensets requiring stable output voltage under varying load
  • Alternator rewinds and rebuilds where the original AVR is obsolete or damaged

Product Description

The R448 is a heavy-duty industrial Automatic Voltage Regulator (AVR) designed for Leroy Somer LSA series brushless alternators equipped with AREP auxiliary windings or Permanent Magnet Generator (PMG) systems. Providing tight steady-state regulation (< ±0.5% RMS), the R448 delivers an impressive 10A continuous excitation current and supports up to 300% short-circuit current forcing (3 IN for 10 seconds), ensuring reliable selective breaker tripping during grid faults.

Leroy Somer AVR R448 Front View

Equipped with Leroy Somer’s patented Load Acceptance Module (LAM), the R448 temporarily reduces terminal voltage by approximately 15% during heavy block load application, shedding effective load by ~25% to prevent prime mover stalling and eliminate black smoke. Its 5-potentiometer control matrix features P1 (Quadrature Droop), P2 (Voltage), P3 (Stability), P4 (Under-frequency / LAM knee), and P5 (Excitation Current Limitation, adjustable 4.5A to 10A).


Technical Specifications Matrix

ParameterOperating Limits & StandardsNotes & Field Conditions
Power Supply SystemAREP auxiliary windings (X1, X2, Z1, Z2) or PMGSustains 300% rated short-circuit forcing current for 10 s
Voltage Sensing Inputs0-110V (95-140V), 0-220V (170-260V), 0-380V (340-520V)5 VA insulated transformer input protects against harmonics
Steady-State Regulation< ±0.5% RMSHigh precision regulation across 4% engine speed variation
Excitation Output RatingContinuous 10A DC, Forcing 10A for 10 secondsP5 trimmer allows ceiling limit adjustment from 4.5A to 10A
Electronic ProtectionOverload / short-circuit / sensing loss latchingExcitation current drops to ~1A after 10s; reset via shutdown
Internal Power Fuse10A slow-blow ceramic fuse cartridgeComprehensive protection for power thyristor bridges
Load Acceptance Module (LAM)Drops terminal voltage ~15% during sudden block loadsSheds effective load by ~25%; cut ST5 wire to suppress
Frequency Selection (ST3)50 Hz with ST3 link / 60 Hz without ST3 linkKnee frequency adjustable via P4 (nominal 48 Hz / 58 Hz)
Parallel Operation DroopQuadrature droop CT input (terminals S1, S2 on strip J2)Accepts ../1A 5 VA Class 1 CT with P1 droop calibration
Dimensions & Weight215 mm × 150 mm × 65 mm; weight: approx. 1.1 kgHeavy-duty metal baseplate with vibration damping

Terminal Connections & Wiring Guide

Leroy Somer AVR R448 Terminal Strip and Trimmer Array

Terminal connections, jumper links, and adjusting controls on the R448 are designated as follows:

Terminal / MarkerFunctional Scope & DesignationWiring & Operational Requirement
X1, X2AREP 1st Auxiliary Winding (Shunt baseline)Connect to alternator stator X1/X2 auxiliary coil leads.
Z1, Z2AREP 2nd Auxiliary Winding (Compound boost)Connect to stator Z1/Z2 leads for load-dependent field forcing.
E+, E-DC Exciter Field Output TerminalsE+ to exciter field positive, E- to negative; never open circuit while running.
0V, 110V, 220V, 380VVoltage Sensing Input TapsWire according to generator line voltage (e.g. 0-380V for 400V sets).
S1, S2 (on strip J2)Parallel Droop Current Transformer TerminalsConnect secondary leads of 1A droop CT mounted on generator phase V.
ST2 LinkTransient Response Speed SelectorFitted: Normal recovery; Open: Fast transient recovery mode.
ST3 LinkOperating Frequency SelectorFitted: 50 Hz operation; Open: 60 Hz operation.
ST4 LinkRemote Voltage Trimmer LinkFitted for local control; remove ST4 to connect 470 Ω (±5%) or 1 kΩ (±10%) pot.
ST5 WireLAM Function Enable / DisableIntact: LAM active; cut wire ST5 to completely suppress the LAM function.
P1 to P5 TrimmersComplete Engineering Adjustment MatrixP1 (Droop), P2 (Voltage), P3 (Stability), P4 (Under-speed knee), P5 (Max field limit).

Leroy Somer AVR R448 Heat Sink Base and Mounting Holes


Potentiometer Calibration Procedure

  1. Initial Trimmer Set-up:
    • Turn P2 (Voltage) fully counter-clockwise.
    • Center P3 (Stability); turn P1 (Droop) fully counter-clockwise.
    • Turn P5 (Excitation limit) fully clockwise (factory default 10A).
    • Verify ST3 jumper matches rated frequency (50 Hz fitted / 60 Hz open).
  2. Voltage Calibration (P2):
    • Bring generator to rated speed (1500 rpm / 50 Hz or 1800 rpm / 60 Hz).
    • Slowly rotate P2 clockwise until generator output reaches rated voltage (e.g. 400 VAC L-L).
  3. Stability Damping Tuning (P3):
    • Rotate P3 clockwise until voltage settles firmly without meter oscillations. If response is sluggish, try removing link ST2 (fast mode) and re-adjust P3.
  4. LAM & Under-Speed Calibration (P4):
    • Lower engine speed to 48 Hz (50Hz sets) or 58 Hz (60Hz sets). Turn P4 counter-clockwise until terminal voltage drops by ~15%; return to rated speed and verify voltage recovers immediately.
  5. Parallel Droop Tuning (P1):
    • Under rated reactive load (PF = 0.8 lagging), verify voltage drops by 2% to 3%. If voltage rises, swap CT leads at S1 and S2. Fine-tune P1 to balance reactive current between paralleled sets.

Field Troubleshooting & Diagnostic Checks

  • No Voltage Output on Start-up:
    • Check internal 10A fuse.
    • If residual voltage is below 5 VAC, stop the engine and flash field terminals E+ (+) and E- (-) with a 12V battery and series diode for 2-3 seconds.
  • Excitation Current Drops to 1A and Voltage Collapses Under Load:
    • Electronic overload protection has latched due to sustained fault (> 10s); clear electrical overload, stop genset to reset AVR, and restart.
  • Reactive Current Circulation Between Paralleled Gensets:
    • Confirm standalone no-load voltages match within ±1V across all sets.
    • Check that droop CT polarity is correct and adjust trimmer P1 on all units to achieve identical 2% to 3% voltage droop slopes.

Generator Automatic Voltage Regulator Leroy Somer AVR R448 — Connection & Terminal Verification

Electrical pinouts, terminal blocks, and sensing wire inputs must match your generator panel layout before applying power.

Terminal & Wiring Notice: Pin assignments and harness connectors can vary between hardware revisions and firmware versions. Never wire terminals based on guesswork or schematics from another model series.

Need help checking terminal compatibility?

Send a clear photo of your existing controller label and rear wire harness to our technical team.

WhatsApp Terminal Verification

Reference Schematics & Terminal Layout

Wiring diagram and terminal reference sheets for Generator Automatic Voltage Regulator Leroy Somer AVR R448 are verified individually by our engineering staff upon inquiry. Contact technical support with your panel layout for the matching schematic.

Technical Manual & Documentation

PDF

Generator Automatic Voltage Regulator Leroy Somer AVR R448 Technical Documentation

Verified POPULACE replacement reference document

Manual (PDF)

FAQ

This POPULACE unit is a compatible replacement for the Leroy Somer AVR R448. Send a photo of your alternator nameplate (model, voltage, frequency) and our engineers confirm the match against R448 before dispatch.

Yes. Output voltage, stability adjustment and protection functions are bench-tested on every unit, and the test record travels with your order.

Leroy Somer AVR R448: overall size 215×150×65mm, shipping weight approx. 1.1kg. Send your panel or packing constraints and we confirm fit.

Leroy Somer AVR R448 is covered by a 13 months factory warranty. Quality issues within the term are replaced or repaired at our cost.

Leroy Somer AVR R448 carries CE,ISO9001 certification from our ISO9001-certified Xiamen facility.

Yes. POPULACE Electronic Co., Ltd. manufactures generator parts in Xiamen, Fujian - factory visits are welcome.

Yes. Samples are available for testing; express freight (FedEx, DHL, UPS, TNT, Aramex) typically delivers within 3-7 days.

In-stock items ship 2-3 days after payment; larger batches are produced in 3-7 days. Sea, air or express shipping is arranged to your preference.

T/T, PayPal, Western Union, MoneyGram, Alibaba order link and RMB transfer are all supported.

Yes. The complete technical manual featuring terminal connection schematics, jumper settings, and calibration procedures can be downloaded directly using the [Manual (PDF)] button on this page.

The complete technical datasheet and installation guide for R448 are available directly through the download button above or under the Manual & FAQ tab.

20 Years Experience for Genset Parts

POPULACE has 20 years of experience supplying generator parts worldwide — reliable, OEM-compatible, and built for continuous operation.

Get a Quote