POPULACE
Generator Automatic Voltage Regulator Leroy Somer AVR R448
Model: R448
Compatible R448 generator AVR at factory wholesale price. 100% bench-tested, 13-month warranty, in stock. Request wiring diagram, datasheet & quote.
| Warranty | 13 months |
|---|---|
| Place of Origin | Fujian, China |
| Brand Name | POPULACE |
| Model Number | R448 |
| Overall Size | 215×150×65mm |
| Weight | 1.1kg |
| Certification | CE,ISO9001 |
| Supply & Excitation System | AREP auxiliary windings (X1, X2, Z1, Z2) or PMG system |
| Voltage Regulation | < ±0.5% RMS steady-state accuracy |
| Excitation Current Capacity | Continuous 10A, Forcing 10A for 10s (limit adjustable via P5: 4.5-10A) |
| Load Acceptance Module | Integrated LAM (~15% voltage drop relief), cut ST5 wire to suppress |
| Paralleling & Sensing | 0-110V/220V/380V sensing; C.T. ../1A droop input with P1 adjustment |
| Lead time | 2-3 days (in stock) |
Applications
- Standby and prime diesel generator sets fitted with Leroy Somer alternators in telecom, data-centre and hospital backup power
- Commercial and industrial gensets requiring stable output voltage under varying load
- Alternator rewinds and rebuilds where the original AVR is obsolete or damaged
Product Description
The R448 is a heavy-duty industrial Automatic Voltage Regulator (AVR) designed for Leroy Somer LSA series brushless alternators equipped with AREP auxiliary windings or Permanent Magnet Generator (PMG) systems. Providing tight steady-state regulation (< ±0.5% RMS), the R448 delivers an impressive 10A continuous excitation current and supports up to 300% short-circuit current forcing (3 IN for 10 seconds), ensuring reliable selective breaker tripping during grid faults.

Equipped with Leroy Somer’s patented Load Acceptance Module (LAM), the R448 temporarily reduces terminal voltage by approximately 15% during heavy block load application, shedding effective load by ~25% to prevent prime mover stalling and eliminate black smoke. Its 5-potentiometer control matrix features P1 (Quadrature Droop), P2 (Voltage), P3 (Stability), P4 (Under-frequency / LAM knee), and P5 (Excitation Current Limitation, adjustable 4.5A to 10A).
Technical Specifications Matrix
| Parameter | Operating Limits & Standards | Notes & Field Conditions |
|---|---|---|
| Power Supply System | AREP auxiliary windings (X1, X2, Z1, Z2) or PMG | Sustains 300% rated short-circuit forcing current for 10 s |
| Voltage Sensing Inputs | 0-110V (95-140V), 0-220V (170-260V), 0-380V (340-520V) | 5 VA insulated transformer input protects against harmonics |
| Steady-State Regulation | < ±0.5% RMS | High precision regulation across 4% engine speed variation |
| Excitation Output Rating | Continuous 10A DC, Forcing 10A for 10 seconds | P5 trimmer allows ceiling limit adjustment from 4.5A to 10A |
| Electronic Protection | Overload / short-circuit / sensing loss latching | Excitation current drops to ~1A after 10s; reset via shutdown |
| Internal Power Fuse | 10A slow-blow ceramic fuse cartridge | Comprehensive protection for power thyristor bridges |
| Load Acceptance Module (LAM) | Drops terminal voltage ~15% during sudden block loads | Sheds effective load by ~25%; cut ST5 wire to suppress |
| Frequency Selection (ST3) | 50 Hz with ST3 link / 60 Hz without ST3 link | Knee frequency adjustable via P4 (nominal 48 Hz / 58 Hz) |
| Parallel Operation Droop | Quadrature droop CT input (terminals S1, S2 on strip J2) | Accepts ../1A 5 VA Class 1 CT with P1 droop calibration |
| Dimensions & Weight | 215 mm × 150 mm × 65 mm; weight: approx. 1.1 kg | Heavy-duty metal baseplate with vibration damping |
Terminal Connections & Wiring Guide

Terminal connections, jumper links, and adjusting controls on the R448 are designated as follows:
| Terminal / Marker | Functional Scope & Designation | Wiring & Operational Requirement |
|---|---|---|
| X1, X2 | AREP 1st Auxiliary Winding (Shunt baseline) | Connect to alternator stator X1/X2 auxiliary coil leads. |
| Z1, Z2 | AREP 2nd Auxiliary Winding (Compound boost) | Connect to stator Z1/Z2 leads for load-dependent field forcing. |
| E+, E- | DC Exciter Field Output Terminals | E+ to exciter field positive, E- to negative; never open circuit while running. |
| 0V, 110V, 220V, 380V | Voltage Sensing Input Taps | Wire according to generator line voltage (e.g. 0-380V for 400V sets). |
| S1, S2 (on strip J2) | Parallel Droop Current Transformer Terminals | Connect secondary leads of 1A droop CT mounted on generator phase V. |
| ST2 Link | Transient Response Speed Selector | Fitted: Normal recovery; Open: Fast transient recovery mode. |
| ST3 Link | Operating Frequency Selector | Fitted: 50 Hz operation; Open: 60 Hz operation. |
| ST4 Link | Remote Voltage Trimmer Link | Fitted for local control; remove ST4 to connect 470 Ω (±5%) or 1 kΩ (±10%) pot. |
| ST5 Wire | LAM Function Enable / Disable | Intact: LAM active; cut wire ST5 to completely suppress the LAM function. |
| P1 to P5 Trimmers | Complete Engineering Adjustment Matrix | P1 (Droop), P2 (Voltage), P3 (Stability), P4 (Under-speed knee), P5 (Max field limit). |

Potentiometer Calibration Procedure
- Initial Trimmer Set-up:
- Turn P2 (Voltage) fully counter-clockwise.
- Center P3 (Stability); turn P1 (Droop) fully counter-clockwise.
- Turn P5 (Excitation limit) fully clockwise (factory default 10A).
- Verify ST3 jumper matches rated frequency (50 Hz fitted / 60 Hz open).
- Voltage Calibration (P2):
- Bring generator to rated speed (1500 rpm / 50 Hz or 1800 rpm / 60 Hz).
- Slowly rotate P2 clockwise until generator output reaches rated voltage (e.g. 400 VAC L-L).
- Stability Damping Tuning (P3):
- Rotate P3 clockwise until voltage settles firmly without meter oscillations. If response is sluggish, try removing link ST2 (fast mode) and re-adjust P3.
- LAM & Under-Speed Calibration (P4):
- Lower engine speed to 48 Hz (50Hz sets) or 58 Hz (60Hz sets). Turn P4 counter-clockwise until terminal voltage drops by ~15%; return to rated speed and verify voltage recovers immediately.
- Parallel Droop Tuning (P1):
- Under rated reactive load (PF = 0.8 lagging), verify voltage drops by 2% to 3%. If voltage rises, swap CT leads at S1 and S2. Fine-tune P1 to balance reactive current between paralleled sets.
Field Troubleshooting & Diagnostic Checks
- No Voltage Output on Start-up:
- Check internal 10A fuse.
- If residual voltage is below 5 VAC, stop the engine and flash field terminals E+ (+) and E- (-) with a 12V battery and series diode for 2-3 seconds.
- Excitation Current Drops to 1A and Voltage Collapses Under Load:
- Electronic overload protection has latched due to sustained fault (> 10s); clear electrical overload, stop genset to reset AVR, and restart.
- Reactive Current Circulation Between Paralleled Gensets:
- Confirm standalone no-load voltages match within ±1V across all sets.
- Check that droop CT polarity is correct and adjust trimmer P1 on all units to achieve identical 2% to 3% voltage droop slopes.
Generator Automatic Voltage Regulator Leroy Somer AVR R448 — Connection & Terminal Verification
Electrical pinouts, terminal blocks, and sensing wire inputs must match your generator panel layout before applying power.
Need help checking terminal compatibility?
Send a clear photo of your existing controller label and rear wire harness to our technical team.
Reference Schematics & Terminal Layout
Technical Manual & Documentation
Generator Automatic Voltage Regulator Leroy Somer AVR R448 Technical Documentation
Verified POPULACE replacement reference document
FAQ
This POPULACE unit is a compatible replacement for the Leroy Somer AVR R448. Send a photo of your alternator nameplate (model, voltage, frequency) and our engineers confirm the match against R448 before dispatch.
Yes. Output voltage, stability adjustment and protection functions are bench-tested on every unit, and the test record travels with your order.
Leroy Somer AVR R448: overall size 215×150×65mm, shipping weight approx. 1.1kg. Send your panel or packing constraints and we confirm fit.
Leroy Somer AVR R448 is covered by a 13 months factory warranty. Quality issues within the term are replaced or repaired at our cost.
Leroy Somer AVR R448 carries CE,ISO9001 certification from our ISO9001-certified Xiamen facility.
Yes. POPULACE Electronic Co., Ltd. manufactures generator parts in Xiamen, Fujian - factory visits are welcome.
Yes. Samples are available for testing; express freight (FedEx, DHL, UPS, TNT, Aramex) typically delivers within 3-7 days.
In-stock items ship 2-3 days after payment; larger batches are produced in 3-7 days. Sea, air or express shipping is arranged to your preference.
T/T, PayPal, Western Union, MoneyGram, Alibaba order link and RMB transfer are all supported.
Yes. The complete technical manual featuring terminal connection schematics, jumper settings, and calibration procedures can be downloaded directly using the [Manual (PDF)] button on this page.
The complete technical datasheet and installation guide for R448 are available directly through the download button above or under the Manual & FAQ tab.
Related Products
Compatible generator parts & matching system accessories.
Technical Guides & Troubleshooting
Engineering diagnostics, terminal wiring diagrams, and parts replacement procedures.
Generator AVR Not Producing Voltage: 5 Causes and How to Test Them
A generator that runs but produces no power is most often an excitation or AVR problem. Here are the five causes we see most in the field, the multimeter check for each, and when the regulator itself needs replacing.
Read Guide → Engineering GuideGenerator Rotating Rectifier Diode Testing: How to Test Forward & Reverse Diodes with a Multimeter
Comprehensive guide to testing generator rotating rectifier assemblies (RSK1001, RSK2001, RSK5001, SSAYEC432). Learn how to diagnose shorted diodes, verify surge varistors, and replace rectifiers.
Read Guide →20 Years Experience for Genset Parts
POPULACE has 20 years of experience supplying generator parts worldwide — reliable, OEM-compatible, and built for continuous operation.