Maintaining stable terminal voltage and rapid transient recovery under fluctuating electrical loads is essential for diesel generator sets powering industrial, commercial, marine, and critical standby facilities. In brushless alternators equipped with Leroy Somer excitation systems, the Automatic Voltage Regulator (AVR) controls excitation power to hold steady-state voltage regulation within ±0.5% to ±1.0%.
Over decades of alternator production, excitation architectures evolved from traditional self-excited Shunt topologies to dual auxiliary winding systems (AREP) and permanent magnet generators (PMG). When maintaining, retrofitting, or repairing generator sets, field engineers and service technicians frequently face the task of replacing legacy or damaged AVR boards such as the R438 or R448 with the universal R450, or servicing compact shunt units like the R120.
This engineering guide provides a technical comparison of Leroy Somer AVR topologies, terminal conversion mappings, potentiometer tuning workflows, and static multimeter diagnostics based on verified technical manual data.
1. Technical Selection & Comparison Matrix
Selecting the correct replacement AVR requires verifying the excitation system, sensing voltage tap, continuous output current, and short-circuit withstand rating. The matrix below summarizes key parameters for the R450 AVR, R438 AVR, R448 AVR, and R120 AVR.
| Engineering Parameter | Leroy Somer R120 | Leroy Somer R438 | Leroy Somer R448 | Leroy Somer R450 |
|---|---|---|---|---|
| Excitation Topology | SHUNT (Self-Excited) | AREP / PMG | AREP / PMG | AREP / PMG / SHUNT |
| Steady-State Regulation | ±1.0% | ±0.5% | ±0.5% | ±0.5% |
| AC Sensing Input | 277V 1-ph / 415V 3-ph (±10%) | 95–140V / 170–260V / 340–528V | 95–140V / 170–260V / 340–528V | 95–140V (110V) / 170–260V (220V) / 340–528V (380V) |
| Power Supply Input | 277 VAC rms (±10%), 50/60 Hz | AREP (X1, X2, Z1, Z2) or PMG | AREP (X1, X2, Z1, Z2) or PMG | Max 150 V, 50/60 Hz (AREP/PMG/Shunt) |
| Continuous DC Output | 4.0 A DC (into ≥15 Ω field) | 4.5 A DC (into ≥10 Ω field) | 6.0 A DC (into ≥10 Ω field) | 6.0 A DC (threshold 1.0–5.5 A adjustable) |
| 10s Overload Output | 6.0 A DC | 8.0 A DC | 10.0 A DC | 10.0 A DC (Max 9.5 A, ceiling 2.9× threshold) |
| Short-Circuit Sustain | None (voltage collapses) | Sustained via AREP/PMG | 300% for 10 s (drops to ~1 A) | 300% for 10 s (trips to 0.5–0.7 A after 10 s) |
| Over-Excitation Protection | Setpoint: 60 VDC (10–85 VDC) | Internal electronic trip | Trips to ~1 A after 10 s >10 A | P3 threshold, 110% rating, 90 s accumulation |
| Loss of Sensing Trip | Integrated detection | Integrated circuit | Integrated circuit | AREP/Shunt: 1 s; PMG: 10 s (current <1 A) |
| Parallel Operation (Droop) | Not standard | Optional CT input | Module R724 / R725A + CT | P4 Droop (0–8% @ 400V, CT 1A/5A secondary) |
| Alternator Frame Match | TAL 040, TAL 042, TAL 044 | LSA 42.2, 43.2, 44.2 | LSA 46.2, 47.2, 49.1 | LSA 46.2, 47.2, 49.1, 50.2 |
For an overview of generator parts cross-referencing across different brands, refer to our Generator Parts Cross Reference Guide.
2. Excitation Topologies: SHUNT vs AREP vs PMG
Understanding the electrical supply architecture is essential when selecting and wiring replacement AVRs on Leroy Somer alternators.
+-----------------------------------------------------------------------------------+
| LEROY SOMER EXCITATION POWER TOPOLOGY ARCHITECTURE |
+-----------------------------------------------------------------------------------+
| |
| 1. SHUNT (R120 / R450 Shunt Mode) |
| Main Stator (Terminals) ----[Power & Sensing]----> AVR ----> Exciter Stator |
| (Simple, economical; excitation collapses during short-circuit or heavy DOL) |
| |
| 2. AREP (R438 / R448 / R450 AREP Mode) |
| Aux Windings: |
| X1 - X2 (Voltage Proportional) ---+ |
| Z1 - Z2 (Current Proportional) ---+--> [Power Supply] |
| Main Stator ---------------------------> [Sensing 0-110/220/380V] --> AVR |
| | |
| Exciter Stator |
| (Provides 300% short-circuit current for 10s without external PMG pilot) |
| |
| 3. PMG (R438 / R448 / R450 PMG Mode) |
| Shaft PMG Rotor/Stator (Independent AC) -> [Power Supply] |
| Main Stator -----------------------------> [Sensing Input] -------> AVR |
| | |
| Exciter Stator |
| (Complete electrical isolation between power source and load transients) |
| |
+-----------------------------------------------------------------------------------+
1. SHUNT Excitation (Self-Excited)
In self-excited setups utilizing the R120 AVR, operating power and voltage sensing are derived directly from the main stator terminals. This provides a compact, cost-effective solution for small standby and prime generators with steady electrical loads. However, if a severe short-circuit or large motor inrush occurs, stator voltage dips sharply, starving the regulator of power and collapsing field excitation.
2. AREP Excitation (Auxiliary Regulated Excitation Principle)
Patented by Leroy Somer, AREP incorporates two dedicated auxiliary windings embedded in the main stator slots:
- X1 - X2 Winding (Voltage-Proportional): Delivers power proportional to the alternator output voltage.
- Z1 - Z2 Winding (Current-Proportional): Delivers power proportional to load current, functioning as an internal booster during heavy load steps or short-circuits.
Because power is generated internally by magnetic flux rather than terminal voltage, AREP-equipped regulators like the R438, R448, and R450 sustain 300% short-circuit fault current for up to 10 seconds, enabling selective downstream circuit breaker tripping without requiring an external pilot generator.
3. PMG Excitation (Permanent Magnet Generator)
A permanent magnet generator mounted on the non-drive end of the shaft supplies independent AC power to the AVR. PMG isolation guarantees that severe waveform distortion from non-linear VFD or thyristor loads cannot interfere with excitation power rails.
3. Terminal Conversion & Replacement: Upgrading to R450
The R450 AVR serves as the primary drop-in replacement for obsolete R448 and R438 boards. Below is the verified terminal conversion table.
| Function | Legacy R448 Terminals | Legacy R438 Terminals | Modern R450 Terminals | Connection Notes |
|---|---|---|---|---|
| Exciter Field Output (+) | E+ / F+ | E+ / F+ | E+ | Connect to exciter stator field positive |
| Exciter Field Output (-) | E- / F- | E- / F- | E- | Connect to exciter stator field negative |
| AREP Aux Winding 1 | X1, X2 | X1, X2 | X1, X2 | Voltage auxiliary supply (or PMG lines) |
| AREP Aux Winding 2 | Z1, Z2 | Z1, Z2 | Z1, Z2 | Current auxiliary booster supply |
| Voltage Sensing Common | 0 V | 0 V | 0 V | Neutral or reference sensing line |
| Voltage Sensing 110V | 110 V | 110 V | 110 V | Sensing range: 95–140 VAC |
| Voltage Sensing 220V | 220 V | 220 V | 220 V | Sensing range: 170–260 VAC |
| Voltage Sensing 380V | 380 V | 380 V | 380 V | Sensing range: 340–528 VAC |
| Quadrature Droop CT | Ext. Module | Optional CT | S1, S2 | Connect 1A or 5A secondary paralleling CT (<2.5VA) |
| External Potentiometer | ST1 / ST2 | ST1 / ST2 | ST1, ST2 | Remove jumper to connect 1 kΩ / 1W external trimmer |
For general AVR sensing and wiring fundamentals, consult our detailed Generator AVR Wiring and Sensing Guide.
+-----------------------------------------------------------------------------------+
| R450 TERMINAL STRIP LAYOUT |
+-----------------------------------------------------------------------------------+
| |
| [ 0V ] [ 110V ] [ 220V ] [ 380V ] [ E- ] [ E+ ] [ S1 ] [ S2 ] |
| |------------ SENSING ----------| |-- FIELD --| |-- CT DROOP --| |
| |
| [ X1 ] [ Z1 ] [ X2 ] [ Z2 ] [ ST1 ] [ ST2 ] [ F1 / F2 FUSES ] |
| |------- POWER SUPPLY -----| |- EXT VOLT -| [ 10A 250V Fuses ] |
| |
| +---------------------------------------------------------------------------+ |
| | ROTARY SWITCH: LAM & U/F Knee Selection (50 Hz / 60 Hz) | |
| | POTENTIOMETERS: P1 (VOLT) P2 (STAB) P3 (I_EXC) P4 (DROOP) | |
| | LED INDICATORS: Green (Normal/Steady) Red (Overload/Trip) | |
| +---------------------------------------------------------------------------+ |
| |
+-----------------------------------------------------------------------------------+
4. Potentiometer Calibration & Commissioning Procedure (R450)
When commissioning a newly installed R450 AVR, calibrate potentiometers P1 through P4 in sequence under controlled operating conditions:
+-----------------------------------------------------------------------------------+
| R450 POTENTIOMETER COMMISSIONING SEQUENCE |
+-----------------------------------------------------------------------------------+
| |
| STEP 1: Initial Preset |
| - P1 (VOLT) counter-clockwise (lowest voltage) |
| - P2 (STAB) mid-position |
| - P3 (I_EXC) clockwise (maximum threshold for initial start) |
| - P4 (DROOP) counter-clockwise (zero droop for single unit) |
| |
| STEP 2: Voltage Adjustment (P1) |
| - Start engine, reach rated speed (1500 RPM @ 50 Hz / 1800 RPM @ 60 Hz) |
| - Slowly adjust P1 clockwise until target voltage (e.g., 400V L-L) is reached |
| |
| STEP 3: Stability Tuning (P2) |
| - Turn P2 counter-clockwise until voltage shows slight hunting or oscillation |
| - Rotate P2 slightly clockwise past the point of stability (critically damped) |
| |
| STEP 4: Excitation Ceiling & Overload Calibration (P3) |
| - Apply full rated load to the generator |
| - Measure excitation current at E+/E- terminals |
| - Adjust P3 clockwise until Green LED remains steady at 110% rated excitation |
| |
| STEP 5: Quadrature Droop Calibration (P4 - Paralleled Sets Only) |
| - Connect 1A or 5A secondary CT across S1/S2 |
| - Apply rated inductive load (PF 0.8) and adjust P4 for 2%–4% voltage droop |
| |
+-----------------------------------------------------------------------------------+
Protection Thresholds & Delay Timings (P3)
- Continuous Threshold Range: Adjustable between 1.0 A and 5.5 A DC.
- Over-Excitation Timing: When excitation exceeds 110% of the P3 setting, the internal counter accumulates 1 count per second for 90 seconds. If the overload condition clears before 90 seconds, the counter counts down at the same rate. After 90 seconds, the AVR clamps excitation to the rated limit.
- Short-Circuit Trip (10s): During a severe short-circuit, the regulator allows up to 2.9× the threshold current (capped at 9.0 A ± 0.5 A, maximum 9.5 A). If the fault persists for 10 seconds, the AVR automatically cuts excitation current to 0.5–0.7 A, protecting exciter windings from thermal burnout.
- Post-Short-Circuit Voltage Limiting: On AREP alternators, voltage is limited to 70% of nominal voltage after a cleared short-circuit until normal steady-state is re-established.
5. Bench Testing & Multimeter Static Checks (R120 & R450)
Before installing a replacement AVR or condemning a suspect board, perform static bench tests using a digital multimeter in diode and resistance modes with the AVR completely disconnected from power.
Static Diode Checks for R120 AVR
- F1 to F2 (Diode Test): Connect the positive meter probe to terminal
F1and the negative probe toF2. The measured reading should be between 0.4 kΩ and 0.6 kΩ (forward diode drop). Reversing the probes should indicate Open Circuit (Infinity). - U to N1 (Resistance Test): Resistance between sensing terminal
Uand neutralN1should measure between 200 kΩ and 260 kΩ. An open circuit indicates an internal sensing circuit failure. - N to F1 (Resistance Test): Resistance between terminal
NandF1should measure very low or near zero ohms. - Internal Protection Fuse: Verify continuity across the 4 A / 240 VAC ceramic fuse on the board.
Static Diagnostics for R450 AVR
- Fuse Check: Verify continuity across both 10 A / 250 V power fuses (
F1/X1andF2/Z2). Blown fuses indicate exciter rotor diode failure, exciter stator short-circuit, or severe auxiliary winding overload. - Power Transistor / Thyristor Check: Check between
X1/X2/Z1/Z2and field outputsE+/E-for shorted internal semiconductors. A zero-ohm reading between power inputs and field output indicates semiconductor puncture. - LED Diagnostic Indicators:
- Green LED On: Normal operation; excitation current is below the continuous threshold.
- Green LED Flashing: Overexcitation timer is actively counting down (load reduced after transient overload).
- Green LED Off / Red LED On: AVR has entered shutdown mode (excitation collapsed to 0.5–0.7 A after a 10s short-circuit or sustained sensing loss).
6. Factory Compatibility & Quality Assurance
POPULACE manufactures precision-engineered compatible replacements for the full range of Leroy Somer voltage regulators, including the AVR R450, AVR R438, AVR R448, and AVR R120.
Every unit is manufactured under ISO9001 quality management, featuring:
- 100% Dynamic Bench Testing: Verified for voltage regulation accuracy, stability response, UFRO knee points, and short-circuit cutoff timing.
- Industrial-Grade Solid-State Components: High-temperature thyristors, metal-film precision potentiometers, and silicone damping encapsulation.
- 13-Month Factory Warranty: Full repair or replacement warranty support.
To verify AVR compatibility for your specific generator set, email your alternator nameplate details and photo to [email protected] or submit an inquiry through our product pages.